DRAW.NO.
3.2.2 TMR
FunctionFunction
The On-Delay Timer (TMR) increments while it receives power flow
and resets to zero when power flow stops. The timer passes power after
the specified interval PV (Preset Value) has elapsed, as long as power is
received. When the On Delay Timer function receives power flow, the
timer starts accumulating time (Current Value (CV)). CV is updated
when it is encountered in the logic to reflect the total elapsed time the
timer has been enabled since it was last reset. This update occurs as
long as the power flow input remains ON. When CV equals or exceeds
the Preset Value (PV), the function begins passing power flow to the
right. When the power flow input transitions from ON to OFF, the
timer stops accumulating time, CV is reset to zero, and Q is turned off.
Output Q is energized when TMR is enabled and PV <= CV.
On delay timer
Name Setting units
TMR_THOUS 0.001 s
TMR_HUNDS 0.01 s
TMR_TENTHS 0.1 s
TMR_SECS 1 s
TMR_TENSEC 10 s
TMR_MIN 1 min
Format
TMR
HUNDS
PV
(EN) (ENO)
???????
ADRS
Parameters
Parameter Data type Meaning
ADRS one-dimensional ADRS is the beginning address of a three-