4. OPERATION
B–61863E/15
PMC PROGRAMMER (SYSTEM P series)
1082
a) Input and alter from keyboard
Set message data in the alter format for both entry and alter. All
characters are settable so long as they can be keyed in from the
SYSTEM P series keyboard.
Key in message data every line in the following format.
“A @@@ MESSAGE–DATA1 NL”.
Message data (maximum 32 characters)
Line number (maximum 3 digits)
A means alter.
b) Delete
Delete message data every line in the following format.
Key in “D@@@
NL”.
Line number to be deleted
c) Search
Search message data by address.
“A@@.@
NL”
Address of message data to be searched
(4) I/O module data (I/O MODULE DATA LIST screen)
I/O module data are used for determining addresses in a sequence
program of each I/O module.
***I/O MODULE DATA LIST***
ADDRESS GROUP BASE SLOT NAME
X000
X001
X002
X003
·
·
·
·
Fig. 4.3.1 (d) I/O module data list screen
a) Input and alter from keyboard
Set I/O module data in the following format when inputting or
altering them from the keyboard.
Key in I/O module data in the format of:
“@@@
@ @ @@ @@@@@ NL”
I/O module name
(maximum 5 digits)
Slot number (maximum 2 digits within
a range of 1 to 10)
Base number (1 digit within a range of 0 to 3)
Group number (1 digit within a range of 0 to 15)
Address (input X0, Y0, ...)