4. PMC BASIC INSTRUCTIONS
B–61863E/15
PMC SEQUENCE PROGRAM
120
4
PMC BASIC INSTRUCTIONS
Designing a sequence program begins with writing a ladder diagram. The
ladder diagram is written using relay contact symbols and functional
instruction code. (These will be described later.) Logic written in the
ladder diagram is entered as a sequence program in the Programmer.
There are two sequence program entry methods. One is the entry method
with the mnemonic language (PMC instructions such as RD, AND and
OR). The other is the relay symbol method (
, and ) in which the
sequence program is entered by using the relay contact symbols and the
functional instruction symbols of the ladder diagram. When the relay
symbol method is used, the ladder diagram format can be used and
programming can be performed without understanding the PMC
instructions (basic instructions such as RD, AND and OR).
Actually, however, the sequence program entered by the relay symbol
method is also internally converted into the instruction corresponding to
the PMC instruction. When the sequence program is punched on a paper
tape and then entered to the programmer, programming must be
performed with the PMC instructions.
Also, the meanings of the functional instructions described later must be
understood fully. See Section 4.1 and Chapter 5.
On how to enter the sequence program into the programmer by using the
PMC instructions and relay symbols, see Chapter III or V.
The following should be noted first before reading the explanation on
PMC instructions.
This manual describes the entry method using mnemonic language.
(1) Signal address
Relay coils and contacts written in a ladder diagram are each given
an address, represented with an address number and a bit number.
(See Fig. 4 (a)) It is possible for the head zero. For details of address,
see Chapter 3.
A B
RO
X8.1
C
Y20.4
Signal name
Relay name
R12.6
R9.0
Bit number
Address number
Fig. 4 (a) Address of signal