4. PMC PARAMETERS SETTING AND
DISPLAY (PMCPRM)
B–61863E/15
PMC OPERATION (CRT/MDI)
474
1 Place the sequence program in the STOP state.
2 When the sequence program is in the RUN state, perform the setting
below.
(1) Set NC to “MDI” mode or “Emergency Stop” status.
(2) Set “PWE” of NC setting screen or Program Protect
Signal(“KEY4”) to 1. (See the following table.)
PWE KEY4
TIMER Ę
COUNTER Ę Ę
KEEP RELAY Ę
DATA TABLE Ę Ę
3 Press the following soft keys to select the screens.
[TIMER ] : TIMER screen
[COUNTR]: COUNTER screen
[KEEPRL] : KEEP RELAY screen
[ DATA ] : DATA TABLE screen
4 By using cursor keys, move cursor to the position for setting value.
5 Press the INPUT key after typing the value.
6 Set “PWE” or “KEY4” to 0 after setting value.
1 This function is effective on the screen of TIMER, COUNTER,
KEEP RELAY, and DATA TABLE.
2 Up to 10 data can be inputted at once.
3 The cursor is moved to the final data position of inputted data.
(1) Input method
D “ ; (EOB)” is used for separating data.
Press the INPUT key after typing “100; 200; 300”.
D “ ; =” is used for inputting the same value as preceding data.
Press the INPUT key after typing “100; =; =; 200; =”, and it
becomes “100, 100, 100, 200, 200”.
D “ ; ; ” is used for skipping an input address.
Press the INPUT key after typing “100; ; 100”.
The second data is not inputted.
4.2
INPUT PMC
PARAMETERS FROM
MDI PANEL
4.2.1
Multiple Data Input