5. EDITING OF SEQUENCE
PROGRAM (EDIT)
B–61863E/15
PMC PROGRAMMER (CRT/MDI)
548
(6) Error and warning messages issued during the editing of assignment
data
No. Error or warning message Description
1 ERR : GROUP NO. (0–15) The group number must be from 0 to 15.
2 ERR : BASE NO. (0–3) The base number must be from 0 to 3.
3 WARN : BASE NO. MUST BE 0 The base number must be 0 for the I/O Unit–B. It is forcibly set to 0.
4 ERR : SLOT NO. (1–10) The slot number must be from 1 to 10 for the I/O Unit–A.
5 ERR : SLOT NO. (0, 1–30) The slot number must be from 0 to 30 for the I/O Unit–B.
6 ERR : SLOT NO. MUST BE 0 The slot number must be 0 to set the power–on/off information for the I/O Unit–B.
7 ERR : ILLEGAL NAME An invalid or unsupported assignment name has been entered. Enter a correct name.
8 INPUT INVALID An invalid character string has been entered. Reenter with a correct format.
9 INPOSSIBLE WRITE An attempt has been made to edit ROM data. ROM data cannot be edited.
10 ERR : ADDRESS ALREADY ASSIGNED The specified address is already assigned. Assign another address or retry after
deleting the existing data.
11 ERR : ADDRESS OVER An address exceeds the upper limit (X127, Y127). Check the addresses used for the
unit to be set.
12 ERR : SLOT ALREADEY DEFINED The specified slot is already assigned. Check the existing data.
13 WARN : SLOT ALREADY DEFINED The specified slot is already assigned. Check the existing data.
14 ERR : UNIT TYPE MISMATCH (IN OR OUT) An X address cannot be assigned to an output module. A Y address cannot be
assigned to an input module.
15 ERR : UNIT TYPE MISMATCH (MODEL) I/O Unit–A and I/O Unit–B are assigned in the same group. I/O Unit–A and I/O Unit–B
cannot exist in the same group.