5. FUNCTIONAL INSTRUCTIONS
B–61863E/15
PMC SEQUENCE PROGRAM
276
(c) ACT and W1 of the DISP instruction
(a) Timing of ACT ON
If EPCB = 0, ACT may be set to 1 with any timing. For instance,
when all display–request bits are off or when the status displayed
on the screen and the display requests are the same, that is, when
there are no new display requests, even if ACT = 1, the DISP
instruction processes nothing and the operation terminates (W1
= 0).
Even if another display–request bit is set on and ACT is set to 1
with a prescribed number of messages (four alarm messages or
one operator messages) displayed on the screen, no message is
displayed for that request, but W1 = 0 after W1 = 1 and W1 = 1
again during execution of the next cycle. In other words, W1 only
changes back and forth between 1 and 0.
(b) Using two or more DISP instructions
If EPCB = 0, ACT of each DISP instruction may be turned on
simultaneously. Until the DISP instruction whose ACT was set
to 1 earlier, has been completed (W1 = 0), executing of the next
DISP instruction is kept waiting. W1 of the DISP instruction kept
waiting remains 0 at this time. Consequently, no messages more
than those specified number are displayed, as discussed in 5.43.1.
From (a) and (b) above, set ACT to 1 whenever EPCB = 0. Do not
set ACT to 1 when EPCB = 1.