B–61863E/15
5. FUNCTIONAL INSTRUCTIONS
PMC SEQUENCE PROGRAM
221
(a) Specify even or odd.
O.E=0 : Even–parity check
O.E=1 : Odd–parity check
(b) Reset
RST=0 : Disables reset.
RST=1 : Sets error output W1 to 0. That is, when a parity error
occurs, setting RST to 1 results in resetting.
(c) Execution command
ACT=0 : Parity checks are not performed. W1 does not alter.
ACT=1 : Executes the PARI instruction, performing a parity
check.
If the results of executing the PARI instruction is abnormal, W1=1 and
an error is posted. The W1 address can be determined arbitrarily.
Fig.5.22.5 shows odd–parity checking of a code signal entered at address
X036.
0
7 6 5 4 3 2 1 0
Address X036
6–bit code signal
Odd–parity bit
PARI
(SUB 11)
A
X036
(2)
R228.0
ERST.M
(1)
X32.7
TF
(0)
F7.3
ERR
R228.0
R228.0
A
A
A
R228.0
Fig. 5.22.5 Ladder diagram for the PARI instruction
CAUTION
For bits 0 to 7, bits other than those for the parity check must
be 0.
5.22.3
Control Conditions
5.22.4
Error Output (W1)
5.22.5
Example of Using the
PARI Instruction