4. OPERATION
B–61863E/15
PMC PROGRAMMER (SYSTEM P series)
1086
00021 WRT R0.1 3 W R0.1 <NL>
00022 RD F1.1 4 R Y1.2 <NL>
00023 WRT R1.1 5 W R1.2 <NL>
6 AE <NL> (Sequential alter end
command)
³ *AS MODE* display disappears
from the lower right part of the
screen.
c) Wiring change function
All of address
used in Ladder Program is changed to a new
address independently of a command. Only bit address can be
changed.
Type in ’CA
Address 1 Address 2 <NL>
A new address
A previous address to be changed
Abbreviation of CHANGE ALL
(Symbol can not be changed)
Example) ’CA R0.1 R1.2 <NL>’
— All ”R0.1” used in Ladder Program is changed
to ”R1.2”.
CAUTION
If an address is specified which can not be changed to a new
address, an alarm 09 occurs when the specified line will be
changed. In that case, previous lines correctly changed to
that line can be acceptable.