8. FUNCTIONS FOR DISPLAYING MEMORY
AREAS AND DEBUGGING
THE PROGRAM (MONIT)
B–61863E/15
PMC PROGRAMMER (CRT/MDI)
610
(1)Display the No.24 of NC parameter.
(2)To connect by Ethernet or HSSB, input ”0”, ”11” or ”12”.
To connect by RS–232C, input ”1”, ”2”, ”11” or ”12”.
Contents of NC parameter No.24.
NC parameter
Setting of the PMC online monitor screen
No.24
RS–232C HIGH SPEED I/F Meanings
NOT CHANGED –
S When ”HIGH SPEED I/F” is not displayed (disabled)
The settings on the screen are enabled as is.
0
NOT USE USE
S When ”HIGH SPEED I/F” is displayed (enabled)
The item of ”RS–232C” is changed to ”NOT USE”.
The item of ”HIGH SPEED I/F” is changed to ”USE”.
1 USE (Channel 1) NOT USE
The item of ”CHANNEL” is set ”1” and the item of ”RS–232C” is
changed to ”USE”.
The item of ”HIGH SPEED I/F” is changed to ”NOT USE”.
2 USE (Channel 2) NOT USE
The item of ”CHANNEL” is set ”2” and the item of ”RS–232C” is
changed to ”USE”.
The item of ”HIGH SPEED I/F” is changed to ”NOT USE”.
11 USE (Channel 1) USE
The item of ”CHANNEL” is set ”1” and the item of ”RS–232C” and
”HIGH SPEED I/F” are changed to ”USE”.
12 USE (Channel 2) USE
The item of ”CHANNEL” is set ”2” and the item of ”RS–232C” and
”HIGH SPEED I/F” are changed to ”USE”.
3 to 10
13 to 254
(Reserved) (Reserved) Don’t use this setting.
255 NOT USE NOT USE
Terminates communication forcibly.It is the same effect as soft key
[EMG ST].
NOTE
1 If the value of No.24 in NC parameter is changed, the setting
of the online monitor screen of PMC is automatically
changed too. This NC parameter is made effective
immediately after changing setting of the parameter.
2 Even if the setting of the online monitor screen of PMC is
changed, the value of No.24 in NC parameter is not
changed
8.5.2.2
How to set at NC
parameter