B–61863E/15
L. MIGRATION OF LADDER PROGRAMS
BETWEEN DIFFERENT MODELS
APPENDIX
1535
– The PMC parameters output from PMC–SB7 cannot be input to
PMC–SA5/SB5/SB6.
The extra relay address (E) is available as PMC address. The PMC
parameters for PMC–SB7 contain the E addresses. When the PMC
parameters for PMC–SB7 are input, the E addresses are overwritten.
(7)Addition of ”LADDER EXEC” in the system parameter (PMC–SB7)
In PMC–SB7, according to addition of ladder level 3, the system
parameter ”LADDER EXEC” is added.
Specify the ladder execution ratio of both level 1 and level 2 in this
parameter.
Defaut value 150 Setting range 1 to 150
– In case that you don’t use level 3 ladder, set the parameter to
maximum value (150).
– In case that you use level 3 ladder, level 3 ladder may not run well
under the maximum value (150). Set the parameter to decrease the
ladder execution time of level1 and level 2.
The ladder execution time of level1 and level2 is calculated as
following formula.
”Ladder execution time of
level1 and level2”
“LADDER EXEC”
100
= 5msec
The ladder execution time of level3 is calculated as following formula.
”Ladder execution time of level3” =
7.5msec – ”Ladder execution time of level1 and level2”.
For example, in case that ”100” is set to the parameter, the ladder
execution time of level1 and levle2 is assigned 5msec in ladder
execution cycle(8msec) and the ladder execution time of level3 is
assigned 2.5msec.
NOTE
Since the level 3 ladder is not required when importing
ladders from the PMC–SA5/SB5/SB6, set this parameter to
the upper limit value (150).
When creating a new level 3 ladder or importing ladders
including the level 3 ladder from, for example, the
PMC–NB6, set this parameter to an appropriate value.