B–61863E/15
5. FUNCTIONAL INSTRUCTIONSPMC SEQUENCE PROGRAM
207
Ę : Can be used
: Cannot be used
PA1 PA3 SA1 SA2 SA3 SA5 SB SB2 SB3 SB4 SB5 SB6 SB7 SC SC3 SC4 NB NB2 NB6
f f
This function can be used for specifying the number of coils only on the
PMC–SB/SC. On other PMCs, specify 0 for the number of coils and use
the common line control end instruction to use this function. For how to
use the instruction, see Subsection 5.18.4.
The specified number of coils or the coils in a region up to the common
line control end instruction (COME) are turned off. (See Fig.5.18.1.1)
Relay number specification is set when a numeric other than zero is
specified in a parameter for the number of turned off coils.
Specification of the region up to the common line control end instruction
is set when zero is specified for the number of turned off coils.
When the common line control end instruction is programmed in the relay
number specification, error is indicated when programming is completed.
COM
SUB 9
ACT
ffff
Number of
turned–off
coils
Effective only when the number of
turned–off coils is set to zero.
0 : Region specification
Other than 0 : Numeric specification
COME
SUB 29
0 to 9999
Fig. 5.18.1.1 Function of COM
5.18
COM (COMMON LINE
CONTROL)
5.18.1
COM (Common Line
Control)
5.18.1.1
Function