3. LADDER DIAGRAM
MONITOR (PMC–SB7)
B–61863E/15
FS16i/18i/21i/0i–B PMC–SA1/SB7 MANIPULATION
886
4. The comment is displayed in the ”COMMENT” field for each
program.
If no comment is set into the subprogram, the ”COMMENT” field
will be blank.
5. The program size is displayed in the ”SIZE (BYTE)” field for each
program.
If the program size is not over 1024 byte, the unit is shown in byte.
If it is over 1024 byte, the unit is shown in kilo (1024) byte with
”K”.
Ex.) The case that program size is not over 1024 byte.
1023 bytes : ”1023” is shown.
Ex.) The case that program size is over 1024 byte.
20000 bytes : ”19.5K” is shown.
6. In the ”NET COUNT” field for each program, total number of nets
in the program and first net number of the program in the whole
Ladder program are displayed as follows.
Total number of nets in the program* / First global net number of
the program in the whole Ladder program*
* Maximum is 99,999.
Displayed with ”–––––” in the case of step sequence program.
7. The status of protection is displayed in the ”P” field for each
program.
Following icons mean the status of protection.
P : Monitoring and editing program are disabled.
R : Monitoring program is enabled. Editing program is
disabled.
(Blank) : Monitoring and editing program are enabled.