4. DESCRIPTION OF PARAMETERS
B–63610EN/01
108
1933 Cs contour control axis (dedicated to the FSSB setting screen)
NOTE
After this parameter has been set, the power must be turned
off then back on for the setting to become effective.
[Data type] Byte axis
[Valid data range] 0, 1
When Cs contour control is to be applied for an axis, this parameter must
be set to 1 for that axis.
NOTE
This parameter is set using the FSSB setting screen. So,
this parameter should not normally have to be specified
directly. This parameter need not be set in FSSB manual
setting 2 mode.
1936 Connector number of the first separate detecter interface unit
1937 Connector number of the second separate detecter interface unit
NOTE
After these parameters have been set, the power must be
turned off then back on for the settings to become effective.
[Data type] Byte axis
[Valid data range] 0 to 7
When a separate detecter interface unit is used, each of these parameters
sets the value obtained by subtracting 1 from a separate detecter interface
unit connector number for each axis. That is, values of 0 through 7 are set
for connector numbers 1 through 8. In addition, bits 6 and 7 of parameter
No.1905 must be set. For an axis that does not use a separate detecter
interface unit, 0 must be set.
Any connector can be used for any axis, however the connectors in a
single separate detecter interface unit should be used in ascending order of
connector number. For instance, connector 4 of a separate detecter
interface unit cannot be used without using connector 3 of the same
separate detecter interface unit.
Example:
Controlled
axis
Connector
number for
the first
separate
detecter
interface unit
Connector
number for
the second
separate
detecter
interface unit
No.1936 No.1937
No.1905
(#7, #6)
X 1 Not used 0 0 0,1
Y Not used 2 0 1 1,0
Z Not used 1 0 0 1,0
A Not used Not used 0 0 0,0