Power Failure Back-up Module
(with control power backup function)
DESCRIPTIONS
TMS01/032E
7.2 Detailed Connection of Cables
The detailed connection of cables connected with Power Failure Backup Module is described in
this section. For the detailed connection of cables connected with amplifier (SVM, SPM, PSM),
see “SERVO AMPLIFIER a series DESCRIPTION” B-65162E/03”.
(1) Detailed Connection of jumper K2
SVM or SPM Power Failure Backup Module Sub Module C
L+ ( i) (ii) (iii) L+
DC link To Sub Module C
L- L-
Film Capacitor : Needed in case that Cable( i) is more than 1.5m and less than 5m.
( i) Connection between Power Failure Backup Module and α amplifiers (SVM, SPM)
Connect the terminal TB1 on Power Failure Backup Module and the terminal TB1 on
SVM or SPM with jumpers or cables. When Sub Module R is connected, the length of
this cable should be shorter than 1.5m. It is possible to lengthen this cable by
maximum 5m on condition that the film capacitor (3.3µF/630V) is added to TB1 on
Power Failure Backup Module.
Recommended Film Capacitor
Manufacturer Name Specification
OKAYA ELECTRIC
INDUSTRY CO.,LTD.
CF99MPP2J335K 3.3µF/630V
Notice: Cable length between Film Capacitor and TB1 is less than 30cm.
Twist lines together or tie lines in parallel.
TB1 Film Capacitor TB1 Film Capacitor
30cm max.
TB1 TB1 TB2 TB1