Power Failure Back-up Module
(with control power backup function)
DESCRIPTIONS
TMS01/032E
8.4 Alarms
The Power Failure Backup Module has the following protection and error detection function.
These protect the machine and the module in the event of an error occurring.
When the alarm occurs at Power Failure Backup Module, Power Failure Backup function
become unavailable. Thus when *ALM goes ”0”, stop the machine operation and turn off the
MCC immediately to protect Power Failure Backup Module.
Alarm
number
Alarm
Name
Description Cause and Countermeasure
1 Insufficient
charge alarm
Sub Module C isn’t
charged completely.
(1) There is misconnection in Terminal TB1 or TB2.
→•The connection to terminal L+ and L− on Sub
Module C is inverted.
•The terminal L+ and L− on Sub Module C is
shorted.
(2) Something wrong with regeneration circuit.
→Replace the Power Failure Backup Module.
2 Low voltage
alarm
DC link voltage become
too low after charging is
completed.
There is something wrong with charging circuit in
Power Failure Backup Module.
→Replace the Power Failure Backup Module.
3 Excessive
regeneration
alarm
Abnormal regeneration
current flowed to the
regeneration resistor.
(1) The regeneration energy exceeded the capacity of
Sub Module R.
→If the total amount of servo motor maximum
output exceed 20kW, use two Sub Module R.
(2) Something wrong with regeneration circuit.
→Replace the Power Failure Backup Module.
4 Regeneration
resistor over
heat
The temperature of
regeneration resistor in
Sub Module R rose to
alarm level.
Discharge current flows through regeneration
resistor continuously in Sub Module R because of the
failure in regeneration circuit.
→Replace the Power Failure Backup Module.
5 Thyristor
drive power
supply low
voltage
The voltage of power
supply for thyristor
driver goes down.
There is something wrong with the power supply for
thyristor driver in Power Failure Backup Module.
→Replace the Power Failure Backup Module.
02 99.06.21 Cause of Alarm 1 corrected.