4.DESCRIPTION OF PARAMETERS B-64120EN/01
- 132 -
1936 Connector number of the first separate detector interface unit
1937 Connector number of the second separate detector interface unit
NOTE
After these parameters have been set, the power
must be turned off then back on for the settings to
become effective.
[Data type] Byte axis
[Valid data range] 0 to 7
When a separate detector interface unit is used, each of these
parameters sets the value obtained by subtracting 1 from a separate
detector interface unit connector number for each axis. That is, values
of 0 through 7 are set for connector numbers 1 through 8. In addition,
bits 6 and 7 of parameter No.1905 must be set. For an axis that does
not use a separate detector interface unit, 0 must be set.
Any connector can be used for any axis, however the connectors in a
single separate detector interface unit should be used in ascending
order
of connector number. For instance, connector 4 of a separate detector
interface unit cannot be used without using connector 3 of the same
separate detector interface unit.
Example
Controlled
axis
Connector
number for the
first separate
detector
interface unit
Connector
number for the
second separate
detector
interface unit
No.1936 No.1937
No.1905
(#7, #6)
X 1 Not used 0 0 0, 1
Y Not used 2 0 1 1, 0
Z Not used 1 0 0 1, 0
A Not used Not used 0 0 0, 0
NOTE
When automatic setting mode is selected for FSSB
setting (when bit 0 of parameter No.1902 is set to
0), these parameters are automatically set when
input is performed with the FSSB setting screen.
When manual setting 2 mode is selected for FSSB
setting (when bit 0 of parameter No.1902 is set to
1), these parameters must be set directly.