B–63503EN–1/01
9. SPINDLE SPEED FUNCTION
440
When multi–spindle control is being used, and TYPE–A is selected (bit
2 (MSI) of parameter No. 3709 is set to 0), the signals for the second
spindle cannot be used.
For details of each signal, see Section 15.4.
#7 #6 #5 #4 #3 #2 #1 #0
G027 *SSTP2 *SSTP1 SWS2 SWS1
PC2SLCG028 GR2 GR1
G029 *SSTP GR21
R08IG032 R07I R06I R05I R04I R03I R02I R01I
SINDG033 SSIN SGN R12I R11I R10I R09I
R08I2G034 R07I2 R06I2 R05I2 R04I2 R03I2 R02I2 R01I2
SIND2G035 SSIN2 SGN2 R12I2 R11I2 R10I2 R09I2
#7 #6 #5 #4 #3 #2 #1 #0
F038 ENB3 ENB2
The parameters for the 1st spindle and the 1st position coder are the same
as usual. This section describes the parameters which are added by this
function.
#7
8133
#6 #5 #4 #3
MSP
#2 #1 #0
NOTE
When this parameter has been set, the power must be
turned off before operation is continued.
[Data type] Bit
MSP Specifies whether to use multi–spindle control, as follows :
0 : Not to use.
1 : Use.
#7 #6 #5 #4 #3 #2 #1 #0
3701 SS2
[Data type] Bit
SS2 The number of connections in serial spindle control
0 : 1
1 : 2
Signal address
Parameter