B–63503EN–1/01
2. PREPARATIONS FOR OPERATION
72
#7
RLSOTG007
#6
EXLM
#5 #4 #3 #2 #1 #0
G110 +LM4 +LM3 +LM2 +LM1
G112 –LM4 –LM3 –LM2 –LM1
#7
BFA1300
#6
LZR
#5 #4 #3 #2
LMS
#1 #0
[Data type] Bit
LMS The EXLM signal for switching stored stroke check 1
0: Disabled
1: Enabled
LZR Checking of stored stroke check 1 during the time from power–on to the
manual position reference return
0: The stroke check 1 is checked.
1: The stroke check 1 is not checked
NOTE
When the absolute–position detector is being used, and the
reference position is already set at power–on, the stored
stroke check is checked immediately after the power is
turned on, regardless of the setting of this bit.
BFA When a command that exceeds a stored stroke check 1, 3 is issued
0: An alarm is generated after the stroke check 1, 3 is exceeded.
1: An alarm is generated before the stroke check 1, 3 is exceeded.
1320 Coordinate value I of stored stroke check 1 in the positive direction on each axis
1321 Coordinate value I of stored stroke check 1 in the negative direction each axis
[Data type] Two–word axis
Increment system IS–B IS–C Unit
Metric input 0.001 0.0001 mm
Inch input 0.0001 0.00001 inch
Rotation axis 0.001 0.0001 deg
[Valid data range] – 99999999 to 99999999
The coordinate values of stored stroke checks 1 in the positive and
negative directions are set for each axis in the machine coordinate system.
The outside area of the two checks set in the parameters is inhibited.
Signal address
Parameter
[Unit of data]