B–64113EN–1/01
2. PREPARATIONS FOR OPERATION
135
[Classification] Input signal
[Function] Switches between stroke limit 1–I (parameter No. 1320 and No. 1321)
and stroke limit 1–II (parameter No. 1326 and No. 1327) for each axis
direction.
[Operation] When this signal goes 1 while DLM (bit 0 of parameter No. 1301) is held
to 1, the control unit operates as described below.
(1)+EXL1 to +EXL4 <G104>
Stroke limit 1 (+ side) is checked using parameter No. 1326 instead of
No. 1320.
(2)–EXL1 to –EXL4 <G105>
Stroke limit 1 (– side) is checked using parameter No. 1327 instead of
No. 1321.
NOTE
If the bit 0 (DLM) of parameter No.1301 is set to 1, the stored
stroke limit switch signal EXLM<G007#6> is disabled.
[Classification] Input signal
[Function] Change the values of the parameters governing the stroke check (1320 and
1321).
[Operation] When these signals are set to 1, the control unit operates as follows:
– Change the stored checks, set with parameter Nos. 1320 and 1321,
to the machine coordinates when the signals are input.
[Classification] Input signal
[Function] Selects whether the stored stroke check 1 limits are checked or not.
[Operation] When this signal is set to 1, the control unit operates as follows:
– Does not check the stored stroke check 1 limits.
Axis direction dependent
stored stroke limit
switch signal
+EXL1 to +EXL4<G104>
–EXL1 to –EXL4<G105>
Stroke check external
setting signals +LM1 to
+LM4 <G110> and –LM1
to –LM4 <G112> (M
series)
Stroke check release
signal RLSOT <G007#7>
(M series)