B–64113EN–1/01
3. MANUAL OPERATION
205
#7
7102
#6 #5 #4 #3 #2 #1 #0
HNGx
[Data type] Bit axis
HNGx Axis movement direction for rotation direction of manual pulse generator
0: Same in direction
1: Reverse in direction
7110 Number of manual pulse generators used
[Data type] Byte
[Valid data range] 1, 2, or 3
This parameter sets the number of manual pulse generators.
Varid data range is below:
1, 2 (T series)
1, 2, 3 (M series)
7113 Manual handle feed magnification m
[Data type] Word
[Unit of data] One time
[Valid data range] 1 to 127
This parameter sets the magnification when manual handle feed
movement selection signal MP2 is on.
7114 Manual handle feed magnification n
[Data type] Word
[Unit of data] One time
[Valid data range] 1 to 1000
This parameter sets the magnification when manual handle feed
movement selection signals MP1 and MP2 are “1”.
7117 Allowable number of pulses that can be accumulated during manual handle feed
[Data type] 2–word
[Unit of data] Pulses
[Valid data range] 0 to 99999999
If manual handle feed is specified such that the rapid traverse rate will be
momentarily exceeded, those pulses received from the manual pulse
generator that exceed the rapid traverse rate are accumulated rather than
canceled. This parameter sets the maximum number of pulses which can
be accumulated in such a case.