B–64113EN–1/01
3. MANUAL OPERATION
203
[Classification] Input signal
[Function] Selects the axis of manual handle feed. A set of four code signals, A, B,
C, and D is provided for each manual pulse generator. (Up to three
generators can be used.) The number in the signal name indicates the
number of the manual pulse generator to be used.
1 First manual pulse generator
2 Second manual pulse generator
3 Third manual pulse generator (M series)
HS 1 A
Code signals A, B, C, and D correspond to the feed axes as listed in the
following table:
Manual handle feed axis selection
HSnD HSnC HSnB HSnA
0000
0001
0010
0011
0100
No selection (None of axis is fed)
1st axis
2nd axis
3rd axis
4th axis
[Classification] Input signal
[Function] This signal selects the distance traveled per pulse from the manual pulse
generator during the manual handle feed or manual handle interrupt. It
also selects the distance traveled per incremental feed step.
The table below lists the signal–to–distance correspondence.
Travel distance
select signal for
manual handle
feed
Distance traveled
MP2 MP1
Manual handle
feed
Manual handle
interrupt
Incremental feed
0
0
1
1
0
1
0
1
Least input
increment 1
Least input
increment 10
Least input
increment m*
1
Least input
increment n*
1
Least command
increment 1
Least command
increment 10
Least command
increment m*
1
Least command
increment n*
1
Least input
increment 1
Least input
increment 10
Least input
increment 100
Least input
increment 1000
*1 Scale factors m and n are specified using parameter Nos. 7113,
7114, 12350, and 12351.
Signal
Manual Handle Feed
Axis Selection Signals
D (M series)
HS1A – HS1D
<G018#0 – #3>
HS2A – HS2D
<G018#4 – #7>
HS3A – HS3D
<G019#0 – #3>
D (T series)
HS1A – HS1D
<G018#0 – #3>
HS2A – HS2D
<G018#4 – #7>
Manual Handle Feed
Amount Selection Signal
MP1, MP2<G019#4, 5>
(Incremental Feed
Signal)