B-75074EN/04 SETTING 5.CIMPLICITY VIEWER
- 231 -
If "Live=True" is not displayed, check the following items:
• On the server PC, activate the FethDgn program and perform
the same check.
If "Live=True" is not displayed also on the server PC, make
the settings on the server PC and subsequent settings again.
• When there is a router between the server and viewer PCs,
you need to check [Connect to Server PC's C4 Services] in
the [Option] menu during "CIMPLICITY VIEWER SETUP"
operation on the viewer PC.
Check the operation in step (8) in "Operation on the i CELL
CIMPLICITY VIEWER Setting Screen on the viewer PC" in
Subsection 5.3.2, "Procedure for Setting the Viewer PC."
5.4.2 Checking CIMPLICITY Viewer Communication
(1) On the server PC
Execute the i CELL project. You do not need to activate [Main
Menu].
(2) On the viewer PC
From the Start menu, select Programs → CIMPLICITY → HMI
→ CIMPLICITY Options to open the CIMPLICITY Options
screen. Then, select the Projects tab and click the [Start as viewer]
button. "VIEWER" is displayed in the [Running projects] field.
(3) On the viewer PC
From the Start menu, select Programs → CIMPLICITY → HMI
→ Point Control Panel.
(4) On the viewer PC
On the Point Control Panel, select Edit → Add Points.
Enter the name of the server PC in the [Project] text box on the
"Select a Point" screen.
(5) Enter "$PROJECT" in the [Point ID] text box on the "Select a
Point" screen and click the [Browse] button. The $PROJECT
point of the project running on the server PC is displayed at the
bottom of the screen as an option. Double-click the point.
(6) When "CIMPROJECT" is displayed as the value of the
$PROJECT point, communication between the server and viewer
PCs is performed.